The selection of the code letter and grouping of equipments by category shall be in
accordance with the circuit function letters specified in MIL-W-5088 wherever appli-
cable. Functional category code letters shall be listed alphabetically (see Figure 4
and 10).
Connected load - column B. All equipment requiring electric
3.5.4.1.2
power from the system analyzed shall be listed in this column.
When the power source supplies its rated capacity
Exception:
plus the requirements of its associated control
devices, these control devices shall not be included
in the listings.
Order of entry.  The equipments listed shall be grouped by
3.5.4.1.2.1
functional category (see 3.5.4.1.1) for each bus. Examples are shown in Figures
4 and 10.
3.5.4.1.2.2
Dummy loads. This type of load, identified as such, shall be
entered as a separate item immediately following the load corrected. If used for ac
system power factor correction, The entry shall be made under "x - ac power".
Similarly, dummy loads used on a dc system shall be listed under "P - dc power".
Transformers.  The type, configuration, and rating of trans-
3.5.4.1.2.3
formers considered as part of the power system shall be listed on the load identifi-
cation charts or given in a note. A separate analysis is not required. The equip-
ment connected to the secondaries of such transformers shall be grouped, together
with the transformer losses, under the proper phases of the primary into which the
phase loads are reflected. See example On Figure 4.
Total number of units - column C. The total number of in-
3.5.4.1.3
stalled units supplied simultaneously by the source being analyzed shall be entered
in this column.
Ac electrical requirements per unit - column D.
3.5.4.1.4
3.5.4.1.4.1
Units. The electric power requirements for each load shall be
stated in watts, vars, and voltamperes, measured at the equipment terminals, with
the nominal system voltage maintained at these terminals. Loads having a leading
power factor shall be identified by an asterisk, with a footnote stating that the
asterisk means leading power factor.
Averaging of requirements. The load requirements for each
3.5.4.1.4.2
unit shall be the average value required by the equipment during the operating time.
Rated load shall be entered for equipments, such as hoists, whose power require-
ments depend on the manner in which they are used.
7