MIL-R-23016(Wep)
ENCLOSURE DATA:  14 GAGE (B&S) ALUMINUM SUGGESTED SIZE 9-3/8 IN. BY 4 BY 4 IN.
FORM DATA:  5-1/4 IN. LENGTH, 3 IN. DIA (OD), .125 IN. WALL DRILL 3/8 IN. HOLE
7/16 IN. FROM EACH END.
WIRE DATA:  AWG 6,600 VOLT, .310 IN. DIA (OD).
COIL DATA: L1 = 5 MICROHENRIES, 13 TURNS SINGLE LAYER, 4 IN. WINDING LENGTH.
CAPACITOR:  C1 SHALL BE MOUNTED ON 1 IN. INSULATING BLOCK ABOVE GROUND.
CAPACITOR DATA: C1 = .1 UF, 600-VOLT DC, BATHTUB.
C2 = 1 UF, 600-VOLT DC, BATHTUB, SINGLE TERMINAL CASE MOUNTED
0N GROUND.
RESISTOR DATA: R1 = 5,000-OHM, 5-WATT CARBON.
1.  THE VALUES GIVEN FOR THE COMPONENT PARTS OF THE NETWORK ARE NOMINAL. REGARD-
LESS OF THE CONSTRUCTION OR DEVIATION FROM NOMINAL VALUES, THE NETWORK MUST HAVE
AN IMPEDANCE WITHIN 20 PERCENT OF THAT GIVEN IN FIGURE 8.
2.  CONNECTING LEADS TO CONDENSERS AND RESISTORS SHOULD BE AS NEARLY AS POSSIBLE
TO ZERO LENGTH.
3.  NETWORKS MAY ALSO BE CONSTRUCTED HAVING A 1-OHM SERIES RESISTOR BETWEEN THE LINE
AND CAPACITOR C2.  THIS 1-OHM RESISTOR SHALL BE MADE UP FROM TEN 1O-OHM, 1-WATT
COMPOSITION RESISTORS.
4.  THE DATA GIVEN IN THIS FIGURE IS SUITABLE FOR THE CONSTRUCTION OF 50-AMPERE
NETWORKS.  LARGER CURRENT-CARRYING NETWORKS MAY BE CONSTRUCTED BY INCREASING THE
WIRE SIZE GIVEN FOR THE COIL AND THE SIZE OF THE OVERALL ENCLOSURE.
5.  THE 50-OHM TRANSMISSION LINE SHOULD BE EXTENDED WITHIN THE ENCLOSURE RIGHT
UP TO THE LOCATION WHERE IT CONNECTS WITH CAPACTOR C1.
6.  CAUTION:  THE NETWORK SHALL BE PROMINENTLY AND PERMANENTLY MARKED "CAUTION - SHOCK
HAZARD - CONNECT CASE TO EARTH GROUND BEFORE CONNECTING A-C POWER LINE."
7.  NETWORKS PROCURED PRIOR TO THE DATE OF THIS SPECIFICATION, BUT MEETING THE
IMPEDANCE REQUIREMENTS OF FIGURE 8, MAY STILL BE USED.
8.  EACH NETWORK SHALL BE PERMANENTLY LABELED WITH THE FOLLOWING DATA: CURRENT RATING
IN AMPERES AND VOLTAGE RATING IN VOLTS AT DIRECT CURRENT, 60, 400, AND 800 CPS.
FIGURE 7 Powerline stabilization network schematic diagram.
66