| MIL-R-6106/14D
ELECTRICAL CHARACTERISTICS:
Magnetic effect: A magnetic compass with a horizontal intensity of 0.18 0.1 gauss shall have its needle
deflected 5 or less when the relay is energized or deenergized.
Voltage transient:
Generation: No greater than 70 volts, decreasing to 50 volts within 20 milliseconds and to 10 volts within 40
milliseconds.
Insulation resistance, initial: 100 megohms.
After life or environmental tests: 50 megohms.
Dielectric withstanding voltage (sea level):
Initial
After life tests
Coil to case
1250 V rms, 60 Hz
1250 V rms, 60 Hz
Auxiliary contacts
1500 V rms, 60 Hz
1250 V rms, 60 Hz
All other points
1500 V rms, 60 Hz
1250 V rms, 60 Hz
Dielectric withstanding voltage (altitude): Not applicable.
Maximum contact drop, initial: 0.150 volt.
After life tests: 0.175 volt.
Overload current: Not applicable.
Rupture current: 400 amperes dc (3 V dc maximum voltage drop).
RFI specification (applicable to coil circuits of ac operated relays): Not applicable.
Part or identifying number (PIN): M6106/14-001.
Qualification testing: Qualification testing shall be in accordance with MIL-PRF-6106, table VIII. No qualification
testing is required for sample numbers 1, 2, 4, 9, or 12. Sample 7 shall have humidity test added between steps
4 and 5. Sample 11 shall have the magnetic effect and voltage transient generation tests, specified by this
specification sheet performed between steps 4 and 5. Sample 6 shall not require sand and dust, vibration, or
minimum current testing.
Retention of qualification: To retain qualification, the manufacturer shall submit group A acceptance reports on a
yearly basis to the qualifying activity.
Quality conformance inspection: Performance of groups B and C tests are not applicable.