MIL-S-17000N(SH)
6.5.9.5.2 Type VIII switchboards.  This drawing shall show the panel
number and switch assembly connector receptacle number with the corresponding
ship cable number arranged in panel number sequence.
6.5.9.6 Wiring details.  A tabulation shall list each segment of internal
switchboard wiring in a form that can be used to actually wire the switchboard.
In addition to the component identification and connection points, this tabula-
tion shall include the wire type, size, and color.  These tabulations shall be
arranged in three groups:  the back section module wiring details, the internal
wiring details of panel-mounted assemblies other than linear movement switch con-
trol circuit wiring (such as meter panels), and harness wiring details from
panel-mounted assembly connectors to module connectors, or other panel-mounted
assembly connectors.  Internal control circuit wiring details of linear movement
switches are specifically omitted since this wiring is identical for all switches.
6.5.9.7 Parts list (electrical).  This drawing shall be a tabulation of
the electrical parts required in a switchboard such as number and types of
switches, connectors, fuses, fuseholders, relays, indicator lights, and terminal
boards.  This drawing is provided for information only.
6.5.9.8 Mechanical guidance drawing.  This drawing shall contain require-
ments for the mechanical configuration of the switchboard.
6.6 Provisioning.  Provisioning Technical Documentation (PTD), spare parts,
and repair parts should be furnished as specified in the contract.
6.6.1 When ordering spare parts or repair parts for the equipment covered
by this specification, the contract should state that such spare parts and
repair parts should meet the same requirements and quality assurance provisions
as the parts used in the manufacture of the equipment.  Packaging for such parts
should also be specified.
6.7 Cross-reference of classification.  Table X lists the switchboard types
covered by the superseded specifications together with the new types covered in
this specification.