| MIL-S-52860D
APPENDIX
TEST METHOD 2
LAS TAMPER SWITCH TOLERANCE TEST
1.
TEST APPARATUS:
a.
Ohmmeter - resolution 10% of reading, accuracy 10% of reading.
b.
Ruler - Graduated in 1/16-inch increments.
2.
TEST PROCEDURE:
a.
Connect ohmmeter between terminals TB1-5 and TB1-6. (Install test
leads through conduit access hole.)
b. Replace cover.
c. Slowly lift the cover. The ohmmeter shall indicate opening of tamper
switch contacts with cover movement between 1/16 and 1/4 inch.
16
|