| ![]() (1) 5 minutes:
no load
3000 watts dc load
(2) 20 minutes:
off
(3) 5 minutes:
4.7.5 Operating temperature. Operate the power supply with full
load at an ambient temperature of 77 degrees F minimum until the temp-
erature rise has stabilized at its maximum value. By means of a de-
vice such as a thermocouple, measure the temperature of the hottest
exposed part, including the enclosure. This temperature shall not
exceed 130 degrees F. Measure the temperature of the front panel and
the operating controls; it shall not exceed 100 degrees F.