| MIL-S-24686A(SH)
of inspe ctions.
4.2
The inspection requirements specified
herein are classified as follows:
(a) First article inspection (see 4.3).
(b) Quality conformance inspection (see 4.4).
4.3 First articl e
pection . When specified (see 6.2), a sample shall be
subjected to the first article inspection. The first article inspection shall
consist of the requirements specified in table IV. One or more failures of any
test shall be cause for rejection.
.
TABLE IV.
Firs t article
Specific
Number of
sample units
requirements
Inspection
See ANSI/UL 199
See ANSI/UL 199
All applicable ANSI/UL 199
performance tests and inspections
Visual and dimensional examination
See 4.4.1
See 4.4.3
4
Shock test
See 3.4.2
Vibration test
4
See 3.4.3
See 3.3
2
Materials Verification
4.4 Qual i ty conforman ce inspection. Quality conformance inspection shall
consist of the inspections and tests shown in table V. Quality conformance
inspection shall be performed on every lot of sprinklers acquired under this
specification.
TABLE V. Ouality conformance ins Pections and tests.
Sampling plan
Test
Inspection/test
Requirement
code letter
I
I
Visual
A
3.7
4.4.1
3.2.3, 3.2.4, 3.2.5
A
Dimensional
4.5.1
Leakage test
A
3.5
4.5.2
A
3.5
Operating temperature
bath test
4.4.1
B
3.6
Marking
4.4.1
Color code painting
3.2.2
B
4.4.1 Visual and dimensional examination. Each sprinkler selected in
accordance with 4.4.3 shall be visually and dimensionally examined for compliance
with the requirements specified in 3.2.3 through 3.2.5 and 3.7.