| MIL-S-55257C(CR)
TABLE VI
Classification of Visual and Mechanical Defects
--
--
Classification
Defects
1.
Mounting plates missing or misloated.
Major
2.
Aircraft loading data plate, instruction
or nameplate omitted, incorrect or illegible.
Welds-cracked or porous. Inspection of
3*
welded assemblies, such as equipment racks en-
trance boxes, etc. should be made prior to
final paint application.
4.
Sealer improperly applied (holes, separations,
or lack of adhesion).
Mounting inserts missing or dislocated.
5.
6.
Burrs or sharp edges in wire duct not removed.
Equipments or bracketry loose or missing.
7.
Doors, etc. inoperative.
8.
Electrical receptacles, switches, jacks, con-
99
nectors, wire ducts, or other electrical com-
ponents loose, improperly located or inoperative.
10.
Locking or holding devices missing or inoperative.
11,
Gaps between sections of wire duct exceed 1/16
inch.
12.
The blower housing or air conditioner mount does
not align properly with the mounting inserts of
the shelter facility.
13.
Ground stud not properly sealed.
14.
Bulkhead power and signal connector.
15.
Electrical schematics missing.
Minor
1.
Doors not easily operable.
2.
Fastening devices difficult to operate.
Finish-abrasions or scratches.
3.
4.
Burrs and sharp edges on brackets not removed.
Screws loose.
5.
6.
Gaskets, not completely and securely adhered.
Electrical schematics not properly adhered to
7.
wall.
Cable assemblies not dressed properly.
8.
22
|